Agree the required fire-system interface with the project fire designer and the fan/controller supplier before selecting the fan. Identify the initiating event, the receiving input, what the fan must do and how it may return to service. A general-purpose stop input is not, by itself, an approved fire-shutdown arrangement.
The NFSA article cited below discusses sprinkler waterflow interlocking in the context of the 2013 edition of NFPA 13. It is useful background, not a declaration of the code edition or arrangement applicable to this building. Existing fire strategy, adopted rules and the reviewing authority control that decision.
Do not promise an AXV-H fire input from a controller photograph or a remote handset. Ask for the exact controller drawing and a written response to the project requirement. If the interface is absent, resolve the design before purchase rather than leaving an installer to invent it.