Use the full label
Put static or total next to the pressure value, not only in a footnote. Keep flow, density and speed alongside it. This is especially useful when several quotations arrive with different curve formats.
Practical Fan Specification Notes
A pressure number without its definition can make a weaker selection look stronger. Keep static and total pressure on separate lines until the basis is clear.
Direct Answer
Compare fan ratings using the same pressure definition, test arrangement and airflow basis. Fan total pressure is based on the difference between outlet and inlet total pressures. Under the standard fan-rating convention, fan static pressure is fan total pressure minus the outlet velocity pressure.
That distinction matters: “fan static pressure” is not automatically the static-pressure difference between any two convenient wall taps. Measurement planes, velocities and installation arrangement affect how a reading relates to the rated quantity.
Ask the supplier to label the curve and selection point explicitly. A total-pressure rating cannot simply replace a required static-pressure value of the same number. Any conversion needs the appropriate velocity and area information, consistent conditions and the applicable rating method.
Engineering scope and sources reviewed 2026-10-19 · Project conditions still govern final selection
Decision Framework
Put static or total next to the pressure value, not only in a footnote. Keep flow, density and speed alongside it. This is especially useful when several quotations arrive with different curve formats.
An outlet duct, free discharge or different inlet arrangement changes the relevant measurement and loss context. Identify the rating arrangement and the proposed installation before treating two curves as equivalent.
A wall tap measures local static pressure under its actual conditions. A traverse or other method may be needed to establish additional quantities. Do not call a single tap reading the fan’s rated pressure without the required method.
AirMoveX Catalog Fit
Linked family is a sourcing starting point, not evidence of the interface, performance or installation approval discussed here. Catalog figures are screening references; confirm the exact variant, duty, installation and project documents before specifying.
Field Inputs
Keep this record with the model-specific proposal and unresolved questions.
| Item | Record Or Request | Why It Matters |
|---|---|---|
| Value | Pressure number, units and static/total label | Prevent a like-number, unlike-quantity comparison |
| Duty | Flow, density and fan speed | Keep the curve point complete |
| Arrangement | Inlet/outlet configuration and rating method | Expose installation differences |
| Planes | Defined measurement locations and required velocities | Support any proposed conversion |
| Evidence | Curve revision and selection report | Keep the accepted basis traceable |
Boundary: No measured pressure or performance rating is shown. The loose probe is not an installed measurement system.
Practical Sequence
Connected Decisions
These links continue the same project workflow rather than sending the reader to loosely related content.
Use this product page to identify a starting configuration. The exact offered variant and its current documents must resolve the open items in this guide.
The chosen instrument and locations must answer the stated pressure question.
A pressure figure alone does not define a useful fan selection.
Convert fan pressure units consistently: 1 conventional in.w.g. is about 249.089 Pa and 1 conventional mm.w.g. is 9.80665 Pa. Keep the pressure definition unchanged.
Questions Buyers Actually Ask
Not generally under the standard fan-rating definition. It is fan total pressure minus outlet velocity pressure.
Not as equivalent ratings. Resolve the definitions and operating conditions first.
No. A complete approved measurement method is needed to relate site readings to the stated fan duty.
No. The fan total-pressure rise depends on the relevant inlet and outlet total pressures and the defined method. An outlet reading alone leaves the inlet and velocity terms unresolved.
Inlet and outlet conditions affect how a rating relates to the proposed installation. Keep the documented arrangement with the duty so a nominal pressure figure is not detached from its basis.
No. First resolve the pressure definition, system requirement and selection basis. A margin does not make unlike quantities comparable and can conceal a wrong duty point.
Source Boundary
These references support the distinctions explained here. External manufacturers’ instructions apply to their named equipment, not automatically to an AirMoveX sourcing reference.
AMCA International
Terminology and rating principles for fan airflow, density, pressure and power. Referencing this handbook does not establish AMCA certification or a tested AirMoveX duty point.
Open sourceProject Review
AirMoveX is an independent sourcing and project-coordination business, not the manufacturer. Send the site record and open questions above. We can coordinate a model-specific proposal and request supporting documents; missing functions or evidence remain unconfirmed until supplied.
Free preliminary fan layout
Send the building. Get a fan layout and price, usually within 24 hours. Length, width, clear height and voltage are enough to start.