Draw the boundary in words
State whether the input is measured at the drive supply, motor terminals or shaft. Include or exclude auxiliary loads explicitly. A quote saying “high efficiency” without that boundary is not a comparable result.
Practical Fan Specification Notes
Two efficiency percentages can disagree because they measure different boundaries. Ask where the power measurement starts before comparing them.
Direct Answer
Wire-to-air efficiency compares defined air power with electrical input at a stated boundary. For compatible SI units, air power is volumetric flow in m³/s multiplied by the selected pressure rise in Pa. Divide that by electrical input in watts, using the same duty and a clearly identified static or total-pressure definition.
Fan shaft efficiency excludes losses upstream of the shaft. Motor efficiency describes a different conversion. Drive input, motor input and fan-shaft power therefore cannot be swapped in the denominator while keeping the same efficiency label.
For arithmetic only, 5 m³/s × 200 Pa = 1,000 W of air power; against 2,000 W of electrical input the result is 50%. These invented inputs are not AirMoveX test results. A valid comparison needs the pressure definition, measurement boundary, operating point and uncertainty.
Engineering scope and sources reviewed 2026-10-19 · Project conditions still govern final selection
Decision Framework
State whether the input is measured at the drive supply, motor terminals or shaft. Include or exclude auxiliary loads explicitly. A quote saying “high efficiency” without that boundary is not a comparable result.
Static-air-power and total-air-power ratios use different pressure terms. Their values cannot be ranked as if they were the same metric. Ask for the test method and installation arrangement supporting the reported number.
Peak efficiency somewhere on a curve does not describe the proposed operating point. Request input power and efficiency at the required flow and pressure, plus part-load information if that is where the fan spends its time.
AirMoveX Catalog Fit
Linked family is a sourcing starting point, not evidence of the interface, performance or installation approval discussed here. Catalog figures are screening references; confirm the exact variant, duty, installation and project documents before specifying.
Field Inputs
Keep this record with the model-specific proposal and unresolved questions.
| Item | Record Or Request | Why It Matters |
|---|---|---|
| Air quantity | Flow, units and density basis | Use the same duty and conditions |
| Pressure | Static or total definition and measurement planes | Calculate the intended air-power term |
| Input | Electrical or shaft boundary and included auxiliaries | Avoid mixing loss boundaries |
| Evidence | Method, operating point and uncertainty | Distinguish test results from estimates |
| Operation | Likely load profile and annual hours | Connect efficiency to a realistic energy question |
Boundary: The numerical example is arithmetic only. The pictured centrifugal assembly is generic, not an AXE-E product image or performance test.
Practical Sequence
Connected Decisions
These links continue the same project workflow rather than sending the reader to loosely related content.
Use this product page to identify a starting configuration. The exact offered variant and its current documents must resolve the open items in this guide.
Useful energy records need the included equipment and operating conditions.
A static-pressure ratio and total-pressure ratio answer different questions.
Questions Buyers Actually Ask
No. Drive, transmission and fan losses may sit outside that motor-only boundary.
With compatible SI units that product is air power in watts, using the chosen pressure definition.
Not for the proposed duty. Request the value and input power at the actual selection point.
No. They use different pressure definitions. Match the useful air-power definition as well as the electrical input boundary before comparing percentages.
No. A motor rating is not a measurement of operating input power at the required duty. Compare the matched system and operating pattern instead.
Request electrical input power or a clearly identified estimate that includes the relevant upstream losses. Shaft power alone does not establish wire-to-air efficiency.
Source Boundary
These references support the distinctions explained here. External manufacturers’ instructions apply to their named equipment, not automatically to an AirMoveX sourcing reference.
AMCA International
Terminology and rating principles for fan airflow, density, pressure and power. Referencing this handbook does not establish AMCA certification or a tested AirMoveX duty point.
Open sourceProject Review
AirMoveX is an independent sourcing and project-coordination business, not the manufacturer. Send the site record and open questions above. We can coordinate a model-specific proposal and request supporting documents; missing functions or evidence remain unconfirmed until supplied.
Free preliminary fan layout
Send the building. Get a fan layout and price, usually within 24 hours. Length, width, clear height and voltage are enough to start.