Series and parallel describe how fan curves combine, not a promise to double installed airflow. In an ideal curve construction, series operation adds the fans' pressure contributions at the same flow. Parallel operation adds their flows at the same pressure. The resulting curve must still meet the system curve.
A worked planning example makes the distinction clear: if each of two identical fans has a valid point of 10,000 m3/h at 100 Pa, ideal series addition produces a combined-curve point of 10,000 m3/h at 200 Pa. Ideal parallel addition produces 20,000 m3/h at 100 Pa. These are invented arithmetic inputs, not AXE-SQ or AXE-E ratings, and neither point is automatically the installed operating point.
The Greenheck reference explains individual fan and system-curve fundamentals. The ideal addition above is this article's engineering explanation, not a quoted series/parallel chapter from that source. Actual arrangements need supported curves, compatibility and a system assessment.