Select each operating stage against the complete air path, including make-up air and stopped-fan openings. Several fans discharging from a shared space do not automatically deliver the number of units multiplied by one free-air catalog rating.
The operating fans interact with the same building pressure and available inlet area. In a suitable parallel arrangement, their combined airflow is considered at a common pressure, then matched to the system. Switching units changes that operating point; it is not simply a proportional change in delivered ventilation.
A stopped fan opening may admit reverse flow when room pressure, wind and other systems favor that route. An appropriate shutter or damper can be part of the design, but it adds resistance and needs a defined closing behavior. The pictured louvers do not establish an airtight seal or a complete control sequence.
Engineering scope and sources reviewed 2026-10-18 · Project conditions still govern final selection