A louver is not sized by its outside dimensions alone. Net free area and pressure loss determine whether replacement air reaches the room without excessive noise or negative pressure.
State the design airflow, louver orientation, rain control, insect screen, filter, face velocity and allowable pressure. Check the path from outdoor opening to occupied zone, not only the louver catalog table.
A louver can be physically large and still have restricted net free area. Louvers, filters, dampers and make-up fans must be included in the same pressure and interlock review as the exhaust fan. There is no universal make-up-air percentage. The correct balance depends on exhaust diversity, process capture, envelope leakage, door operation and the pressure target.